Small Type Hot Water Absorption Chiller Parameters
Model RXZ-11 RXZ-23 RXZ-35 RXZ-58 RXZ-115 RXZ-175 RXZ-230 RXZ-290 RXZ-350
Cooling Capacity Kw 11 23 35 58 115 175 230 290 350
Hot Water Flow Rate m3/h 2.9 5.8 8.6 14.3 28.5 42.8 57.0 71.0 85.3
Inlet/Outlet Temp. 90 / 85 ℃
Inlet/Outlet Dia. DN25 DN40 DN40 DN50 DN65 DN80 DN100 DN100 DN100
Pressure Loss MPa 0.08 0.04 0.04 0.05 0.05 0.05 0.06 0.06 0.06
Chilled Water Flow Rate m3/h 2.0 4.0 6.0 10.0 20.0 30.0 40.0 50.0 60
Inlet/Outlet Temp. 15 / 10℃
Inlet/Outlet Dia. DN25 DN32 DN40 DN50 DN65 DN65 DN80 DN80 DN100
Pressure Loss MPa 0.06 0.03 0.03 0.04 0.05 0.05 0.05 0.05 0.05
Cooling Water Flow Rate m3/h 5 10.0 15.0 25.0 50.0 75.0 100 .0 125.0 150
Inlet Temp. 30℃
Inlet/Outlet Temp. DN32 DN40 DN50 DN65 DN80 DN100 DN125 DN125 DN150
Pressure Loss MPa 0.05 0.04 0.04 0.05 0.05 0.05 0.06 0.06 0.06
Dimension Length mm 600 1010 1410 1800 2755 2305 3105 2800 3700
Width mm 700 785 785 920 970 1160 1160 1600 1600
Height mm 1900 1622 1622 1820 1990 2280 2280 2400 2400
Power Consumption Kw 0.15 0.3 0.3 0.3 0.37 0.9 1.1 1.1 1.1
Shipping Weight Kg 400 730 1100 1600 2600 3700 4700 5800 6500
Else
  1. The unit includes lithium bromide absorption chiller, control box, vacuum pump and hot water adjusting valve.
  2. Fouling factor for chiller water is 0.086m2℃/KW。
Small Type Hot Water Absorption Chiller Flow Sample