Gas Fired Chiller Heater Parameters
Model ZRX-23 ZRX-35 ZRX-58 ZRX-115
Cooling Capacity Kw 23 35 58 115
Heating Capacity Kw 23 35 58 115
Natural Gas Cooling Consumption m3/h 2.5 3.7 5.8 11.5
Heating Consumption m3/h 3.0 4.4 6.8 13.5
Pressure mmH2O 200~650
Air Water Chilled Water Inlet/Outlet Temp. 12/7℃
Hot Water Inlet/Outlet Temp. 55/60℃
Flow Rate m3/h 4.0 6.0 10.0 20.0
Inlet/Outlet Dia. DN32 DN32 DN50 DN65
Pressure Loss MPa 0.03 0.03 0.04 0.05
Power Consumption of Cooling Kw 1.8 3.2 5.2 7.2
Power Consumption of Heating Kw 0.7 1.2 1.7 2.4
Dimension Length mm 1600 1950 1950 5200
Width mm 1600 1950 3000 2000
Height mm 2300 2300 2300 2300
Shipping Weight Kg 850 1500 2200 3500
Else
  1. For fuel: natural gas, town gas, liquefied petroleum gas, diesel. Order to be sure one of them。In table natural gas calorific value by the 10kWh/m3.
  2. The above unit includes lithium bromide absorption chiller, control box, cooling water tower, chilled water pump, cooling water pump, burner ,filter of chilled & cooling water, vacuum pump.
  3. Fouling factorr is 0.086m2℃/Kw, Max pressure of f air wate water: ≤ 0.4MPa.
  4. Refrigeration standard of the climate conditions: Atmospheric temperatures 36 ℃, Wet bulb temp: 27℃.