Hot-Water/Direct-fired Single/Double Effect Absorption Chiller/Heater Parameters
Model 58 95 190 285 380
Cooling Capacity(Hot+Fuel) Kw 58 95 190 285 380
Cooling Capacity(Hot Only) Kw 35 58 115 175 230
Heating Capacity Kw 54 88 176 265 355
Air Water Cooling 12--7℃(11--8℃ when hot only)
Heating 55.4--60℃
Flow Rate m3/h 10 16.4 32.8 49.1 76
Inlet/Outlet Dia. DN40 DN50 DN65 DN80 DN100
Pressure Loss MPa 0.08 0.08 0.08 0.08 0.08
Cooling Water Inlet/Outlet Temp. 30--37℃
Flow Rate m3/h 18 30 60 90 120
Pressure Loss MPa 0.08 0.08 0.08 0.09 0.09
Inlet/Outlet Dia. DN50 DN65 DN100 DN125 DN125
Hot Water Inlet/Outlet Temp. 90--85℃
Flow Rate m3/h 8.6 14.3 28.5 42.8 57.0
Pressure Loss MPa 0.08 0.08 0.09 0.09 0.09
Inlet/Outlet Dia. DN40 DN50 DN65 DN80 DN100
Fuel Consumption
(Cooling/Heating)
Diesel Oil Kg/h 4.4/4.9 7.2/7.9 14.3/15.8 21.4/23.6 28.5/31.5
Coal Gas Nm3/h 11.8/13.1 19.2/21.4 38.4/42.7 57.6/64.0 76.8/85.3
Natural Gas Nm3/h 4.1/4.6 6.65/7.4 13.3/14.8 20.0/22.1 26.6/29.5
Electricity Consumption Kw 0.75 0.90 1.7 2.1 2.5
Dimension Length mm 1700 1900 2820 2550 3300
Width mm 1450 1600 1950 2300 2400
Height mm 1800 2000 2200 2450 2450
Shipping Weight Kg 1800 2700 3600 5100 6800
Hot-Water/Direct-fired Single/Double Effect Absorption Chiller/Heater Flow