Integrated Hot-water Chiller Parameters
Model TX-11 TX-23 TX-35 TX-58 TX-115 TX-175 TX-230 TX-290 TX-350
Cooling Capacity Kw 11.5 23 35 58 115 175 230 290 350
Hot Water Flow Rate m3/h 2.9 5.8 8.6 14.3 28.5 42.8 57.0 71.0 85.3
Inlet/Outlet Temp. 90 / 85℃
Inlet/Outlet Dia. DN25 DN40 DN40 DN50 DN65 DN80 DN100 DN100 DN125
Pressure Loss MPa 0.08 0.04 0.04 0.05 0.05 0.05 0.06 0.06 0.06
Chilled Water Flow Rate m3/h 2.0 4.0 6.0 10.0 20.0 30.0 40.0 50.0 60
Inlet/Outlet Temp. 15 / 10℃
Inlet/Outlet Dia. DN25 DN32 DN32 DN50 DN65 DN65 DN80 DN80 DN100
Pressure Loss MPa 0.06 0.03 0.03 0.04 0.05 0.05 0.05 0.05 0.05
Power consumption Kw 1.0 1.7 2.3 2.8 5.3 10.0 13.8 17.5 21.2
Dimension Length mm 1675 1675 1950 3050 3500 3000 3500 2800 3700
Width mm 1675 1675 1825 1900 1100 1780 1780 1600 1600
Height mm 2130 2130 2130 2375 2160 2450 2450 2400 2400
Shipping Weight Kg 1000 1000 1500 2200 3300 4100 5000 6200 7000
Including or Excluding Cooling Towers Include Excluding
Else
  1. The above unit includes lithium bromide absorption chiller, control box, cooling water tower, chilled water pump, cooling water pump, hot water adjusting valve,filter of chilled & cooling water, vacuum pump.
  2. Fouling factor for chiller water is 0.086m2℃/KW.
  3. Refrigeration standard of the climate conditions: Atmospheric temperatures 36 ℃,Wet bulb temp: 27℃.
Integrated Hot-water Chiller System Flow