Low Temperature Hot-water Chiller Parameters
Model RXZ-35D RXZ-58D RXZ-81D RXZ-115D RXZ-175D RXZ-230D RXZ-290D
Cooling CapacityKw 350 580 810 1150 1750 2300 2900
Chilled Water Flow Rate m3/h 60 100 140 200 300 400 500
Inlet/Outlet Temp. 12/7℃
Inlet/Outlet Dia. DN100 DN125 DN150 DN150 DN200 DN250 DN250
Pressure Loss MPa 0.08 0.08 0.08 0.08 0.09 0.09 0.09
Cooling Water Flow Rate m3/h 146 243 349 486 729 972 1215
Inlet/Outlet Temp. 30/35℃
Inlet/Outlet Dia. DN150 DN200 DN250 DN250 DN300 DN350 DN400
Pressure Loss MPa 0.09 0.09 0.09 0.10 0.10 0.10 0.10
Hot Water Flow Rate m3/h 42.9 71.5 100 143 214 286 357
Inlet/Outlet Temp. 95/85℃
Inlet/Outlet Dia. DN100 DN100 DN125 DN125 DN150 DN200 DN250
Pressure Loss MPa 0.08 0.08 0.08 0.08 0.09 0.10 0.10
Power Consumption Kw 1.5 1.5 3.0 3.0 10.0 12.5 12.5
Dimension Length mm 3700 3800 4500 4800 7100 6850 7580
Width mm 1600 1900 1900 2100 2100 2500 2500
Height mm 2400 2400 27100 3100 3100 3400 3400
Shipping Weight Kg 6500 8500 12300 15800 25600 33200 40600
Else
  1. The pressure of chilled water, cooling Water, and hot water are less than 0.8MPa.
  2. Fouling factor for chiller water is 0.086m2k/kw.
High Temperature Hot-water Chiller Parameters
Model RXZ-35D RXZ-58D RXZ-81D RXZ-115D RXZ-175D RXZ-230D RXZ-290D
Cooling Capacity Kw 350 580 810 1150 1750 2300 2900
Chilled Water Flow Rate m3/h 60 100 140 200 300 400 500
Inlet/Outlet Temp. 12/7℃
Inlet/Outlet Dia. DN100 DN125 DN150 DN150 DN200 DN250 DN250
Pressure Loss MPa 0.08 0.08 0.08 0.08 0.09 0.09 0.09
Cooling Water Flow Rate m3/h 120 200 280 400 600 800 1000
Inlet/Outlet Temp. 30/36℃
Inlet/Outlet Dia. DN150 DN200 DN250 DN250 DN300 DN350 DN400
Pressure Loss MPa 0.09 0.09 0.09 0.10 0.10 0.10 0.10
Hot Water Flow Rate m3/h 14.1 23.5 32.9 46.9 70.4 93.9 117.3
Inlet/Outlet Temp. 125/95℃
Inlet/Outlet Dia. DN65 DN80 DN80 DN100 DN125 DN150 DN150
Pressure Loss MPa 0.08 0.08 0.08 0.08 0.09 0.10 0.10
Power Consumption Kw 1.5 1.5 3.0 3.0 10.0 12.5 12.5
Dimension Length mm 3300 3700 5100 4800 6500 7300 7800
Width mm 1400 1500 1500 1900 2300 2300 2400
Height mm 2200 2300 2300 2100 2980 2980 3100
Shipping Weight Kg 5300 6900 9200 13800 19700 27500 34300
Else
  1. The pressure of chilled water, cooling Water, and hot water are less than 0.8MPa.
  2. Fouling factor for chiller water is 0.086m2k/kw.